Skip to Content
Dehumidifiers

FH - GH Series

Efficient dehumidification for underfloor heating installations.

  • Capacity:20 to 164 l/24h
  • Air flow:250 to 1850 m³/h
  • Refrigerant:R134a / R407C
  • Installation:Vertical or ducted
Efficient dehumidification for underfloor heating installations.

Technology

  • Galvanised structure
  • Pre/post cooling battery
  • Centrifugal fans
  • Microprocessor control
Request Quote

GENERAL FEATURES

The FH and GH series dehumidifiers are designed to work with underfloor heating systems, providing precise humidity control and ensuring optimal comfort conditions. They incorporate pre and post treatment batteries that allow for adjustment of the treated air temperature, even when operating without hydraulic support.

Main Components

Construction and Components

Joinery

All units in the FH-GH series are made of hot-dip galvanised sheet metal to ensure the best resistance to corrosion. The framework consists of removable panels to facilitate inspection and maintenance of the internal components. The condensate tray is supplied as standard with all units and is made of plastic for model 25, and sheet metal for models 50-100-200.

Refrigeration circuit

The refrigeration circuit is made with components from leading international companies and in accordance with current regulations. The refrigerant gas used is R134A (model 25) and R407C (models 50-100-200). The circuit includes a dehydrator filter, expansion capillaries, and a Schrader valve for maintenance and control.

Compressors

The compressors are of the reciprocating type (for model 25) or the rotary type (for models 50-100-200), with a thermal protection relay. The compressor is mounted on a rubber anti-vibration support to reduce noise and vibrations.

Condensers and evaporators

The condensation and evaporation coils are made with copper tubing and aluminium fins. The tube has a diameter of 3/8” and the thickness of the fins is 0.1 mm.

Ventilation

Centrifugal fans designed to ensure a constant airflow and efficient operation in ducted installations.

Filtration

Easily removable air filters for cleaning, ensuring adequate air quality and protection of internal components.

Technical Specifications

FH - FHWZ
Parameter 25 25WZ
Humedad absorbida (1)l/24h20.120.1
Cooling power (W)W1250
Absorbed power (W)W360360
Maximum absorbed power (W)W440440
Corriente nominal absorbidaA2,72,7
Intensidad de arranqueA18,118,1
Caudal de airem³/h250250
RefrigerantR134aR134a
GWP14301430
Carga de gaskg0,20,6
Carga en CO₂ equivalentet0,360,89
Caudal agual/h150150
Pérdida de cargakPa87.8
Potencia sonora (2)dB(A)4343
Presión sonora (2)dB(A)3030
Power supplyV/Ph/Hz230/1/50230/1/50
GH - GHWZ
Parameter 25 25WZ 50 50WZ 100 100WZ 200 200WZ
Humedad absorbida (1)l/24h20.120.148.648.687.587.5164.5164.5
Cooling power (W)W15003800690012100
Absorbed power (W)W3403407007001450145024502450
Maximum absorbed power (W)W440440119011901850185032003200
Corriente nominal absorbidaA2.92.95.25.28.58.514.614.6
Intensidad de arranqueA18,318,321,321,332,832,855,655,6
Caudal agual/h150150500500600600900900
Pérdida de cargakPa8.07.817.042.032.039.548.064.0
Caudal de airem³/h2502506006001000100018501850
Presión disponible (vel. máx)Pa434360607575120120
RefrigerantR134aR134aR407CR407CR407CR407CR407CR407C
GWP14301430177417741774177417741774
Carga de gaskg0,20,60,70,91,01,61,72,0
Carga en CO₂ equivalentet0,280,861,241,601,772,833,023,55
Potencia sonora (2)dB(A)4545505057576464
Presión sonora (2)dB(A)3737373743435050
Power supplyV/Ph/Hz230/1/50

(1) Condiciones: T. aire entrada 30°C - H.R. 80%
(2) Medida a 1 metro de distancia