SRH Series
High-efficiency dehumidifiers with heat recovery for demanding applications.
- Application:Industrial / swimming pools / processes
- Installation:Ducts
- Refrigerant:R410A
- Function:Dehumidification with heat recovery
GENERAL FEATURES
The SRH series has been developed for applications where not only precise humidity control is required, but also efficient energy management through heat recovery systems. These units allow for the utilisation of heat generated during the dehumidification process, reusing it for heating air or water, which results in a significant reduction in the overall energy consumption of the installation. Their design is aimed at industrial applications, indoor swimming pools, and production processes, where continuous, stable, and highly efficient operation is required. The SRH series guarantees high performance even in demanding conditions, ensuring the stability of processes and the protection of installations and materials against humidity.
Construction and Components
Structure and carpentry
The SRH units are made of high-strength galvanised steel with anti-corrosion treatment, designed to operate in aggressive environments and high humidity.
Their robust design allows for continuous operation in industrial conditions, ensuring structural stability and a long service life.
Refrigeration circuit
Optimised circuit with R410A refrigerant, designed to maximise performance and energy efficiency in intensive dehumidification processes.
Includes control and safety components that ensure the reliability of the system.
Heat recovery
Thermal recovery system that allows for the utilisation of energy extracted from humid air, which can be used for heating air or water.
This system significantly improves the overall energy efficiency of the equipment.
Compressors
High-performance compressors designed for continuous operation in demanding applications, with high efficiency and reliability.
Heat exchange coils
High-efficiency copper and aluminium coils designed to maximise thermal exchange and ensure consistent performance.
Ventilation
High-performance centrifugal fans that ensure uniform air distribution in ducted installations.
Defrosting system
Automatic system that prevents ice formation, ensuring continuity of operation.
Control and regulation
Microprocessor control that manages all system parameters, optimising consumption and performance.
Installation Diagram
Technical Specifications
| SRH | 1100 | 1300 | 1500 | 1800 | 2200 | 3000 |
|---|---|---|---|---|---|---|
| Absorbed Humidity (l/24h) | 1137.0 | 1289.0 | 1486.0 | 1868.0 | 2314.0 | 3061.0 |
| Nominal Absorbed Power (kW) | 14.1 | 16.5 | 19.3 | 23.6 | 27.6 | 37.2 |
| Maximum Absorbed Power (kW) | 21.7 | 23.0 | 30.5 | 35.9 | 42.0 | 61.0 |
| Nominal Absorbed Current (A) | 37.4 | 37.6 | 49.8 | 58.4 | 81.2 | 98.8 |
| Starting Current (A) | 116.0 | 102.0 | 132.0 | 136.0 | 220.0 | 283.0 |
| Hot Water Battery (kW) | 72 | 88 | 94 | 112 | 125 | 155 |
| Air Flow (m³/h) | 9500 | 10500 | 13000 | 15000 | 17000 | 25000 |
| Available Pressure (Pa) | 250 | 250 | 250 | 250 | 250 | 250 |
| Refrigerant | R407C | R407C | R407C | R407C | R407C | R407C |
| GWP | 1774 | 1774 | 1774 | 1774 | 1774 | 1774 |
| Gas charge (kg) | 13.0 | 14.0 | 22.0 | 25.0 | 25.0 | 37.5 |
| CO₂ equivalent charge (t) | 23.06 | 24.836 | 39.03 | 44.35 | 44.35 | 66.52 |
| Sound power (dB(A)) | 79 | 80 | 82 | 82 | 83 | 84 |
| Sound pressure (dB(A)) | 63 | 64 | 65 | 65 | 66 | 66 |
| Power supply | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |