GENERAL FEATURES
The SBA HT series has been specifically developed for applications in indoor swimming pools and wellness centres where, in addition to precise humidity control, high energy efficiency is required through the recovery of heat generated during the dehumidification process. These units allow for the maintenance of optimal environmental conditions, preventing the formation of condensation on walls, ceilings, and glazed surfaces, which helps to preserve the structural integrity of the building and improve user comfort.
Construction and Components
Structure and carpentry
Manufactured from galvanised steel with anti-corrosion treatment, the SBA HT units are designed to operate in environments with high humidity and the presence of corrosive agents. Their modular design facilitates access to internal components.
Refrigeration circuit
The refrigeration circuit uses refrigerant R410A and is optimised to operate continuously under demanding conditions, ensuring stability and high performance.
Heat recovery
They incorporate heat recovery systems that allow the energy extracted from the humid air to be used for heating the air or the pool water, increasing the energy efficiency of the system.
Ventilation
High-performance fans designed to ensure uniform air distribution and adapt to both ambient and ducted installations.
Electronic control
Microprocessor control system that automatically regulates the operating cycles, optimising energy consumption and maintaining the desired environmental conditions.
Corrosion protection
Components treated to withstand aggressive environments, especially in pool applications where humidity and chemicals can affect the equipment.
Installation diagram
Technical specifications
| SBA A-P | 036 | 056 | 076 | 116 | 156 | 163 |
|---|---|---|---|---|---|---|
| Humidity absorbed at 35°C - 80% (l/24h) | 42.0 | 75.9 | 90.4 | 151.9 | 168.8 | 185.7 |
| Humidity absorbed at 30°C - 80% (l/24h) | 35.6 | 60.9 | 72.4 | 124.9 | 141.6 | 148.8 |
| Moisture absorbed at 30°C - 60% (l/24h) | 25.4 | 42.4 | 51.9 | 96.8 | 107.2 | 110.9 |
| Moisture absorbed at 27°C - 60% (l/24h) | 22.1 | 35.7 | 44.0 | 83.5 | 93.7 | 94.1 |
| Nominal absorbed power (1) (kW) | 0.5 | 0.7 | 0.9 | 1.3 | 1.8 | 2.2 |
| Maximum absorbed power (2) (kW) | 0.7 | 1.2 | 1.2 | 2.0 | 2.7 | 3.0 |
| Support electric resistance (kW) | 3.0 | 3.0 | 3.0 | 6.0 | 6.0 | 4.5 |
| Maximum absorbed current (2) (A) | 3.5 | 5.5 | 5.4 | 9.2 | 12.2 | 6.6 |
| Starting current (A) | 14.3 | 19.4 | 19.9 | 27.7 | 40.8 | 28.8 |
| Hot water battery (kW) | 3.5 | 7.0 | 7.0 | 11.5 | 11.8 | 11.8 |
| Air flow (m³/h) | 500 | 650 | 650 | 1500 | 1500 | 1500 |
| Refrigerant | R410A | R410A | R410A | R410A | R410A | R410A |
| GWP | 2088 | 2088 | 2088 | 2088 | 2088 | 2088 |
| Gas charge (kg) | 0.30 | 0.50 | 0.52 | 1.00 | 1.20 | 1.20 |
| CO₂ equivalent charge (t) | 0.63 | 1.04 | 1.09 | 2.09 | 2.51 | 2.51 |
| Sound power (dB(A)) | 54 | 57 | 57 | 59 | 59 | 61 |
| Sound pressure (dB(A)) | 40 | 43 | 43 | 44 | 44 | 46 |
| Power supply | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3+N/50 |